Technical Specifications:
TECHNOLOGY
On-line double-conversion
FORMAT
Convertible tower/rack
INPUT
Rated voltage
200 / 208 / 220 / 230 / 240 V (1)
Voltage range 60% load
110 ÷ 300 V up to 60% load
Rated frequency
50 / 60 Hz (auto-detection)
Frequency range
±10 Hz
Total harmonic distortion (THDi)
?5%
Auto~detection of frequency
Yes
OUTPUT
Power factor
1
Waveform
Pure sine wave
Rated voltage
200 / 208 / 220 / 230 / 240 V (1)
Voltage accuracy
±1%
Power (VA/W)
3000 / 3000
Total harmonic distortion (THDv)
< 2% linear load / < 4% non-linear load
Synchronised frequency
±3 Hz
Free running frequency
±0.1 Hz
Frequency
50 / 60 Hz
On-line performance
≥89 ÷ 91%
Eco-mode performance
≥95 ÷ 97%
Admissible overloads
< 130% for 5 min / < 140% for 30 s / <150 % for 1.5 s / 150 % for 100 ms
Socket type
IEC
No. Of sockets
8 + 1
Programmable sockets
Yes, for critical / non-critical loads (4/4)
BYPASS
Rated voltage
200 / 208 / 220 / 230 / 240 V (1)
Frequency range
50/60Hz ±10 Hz
BATTERY
Battery type
Pb-Ca sealed, AGM, maintenance-free
Charge type
I/U (constant current/constant voltage)
Recharge time
3 hours to 95%
CHARGER
Temperature voltage compensation
Yes
COMMUNICATION
Ports
USB-HID / RS-232
Intelligent slot
Slot for SNMP/potential-free contacts/ MODBUS
Monitoring software
For Windows, Linux and Mac
INDICATIONS
Type
LCD + keypad
OTHER FUNCTIONS
Cold start (start-up from batteries)
Yes
Emergency stop (EPO)
Yes
ADSL/fax/modem transient protector
Yes
OPERATING MODES
Frequency converter (CVCF)
Yes (2)
GENERAL
Operating temperature
0º C ÷ 55º C(3)
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
2,400 masl (power degradation up to 5,000 m)
Acoustic noise at 1 metre
< 50 dB
STANDARDS
Safety
EN-IEC 62040-1
Electromagnetic compatibility (EMC)
EN 62040-2(C2)
Operation
VFI-SS-11 (EN-62040-3)
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
605
Width (mm)
438
Height (mm)
88
WEIGHT
Weight (kg)
27.5