Technical Specifications:
TECHNOLOGY
On-line double conversion
FORMAT
Tower
INPUT
Voltage
220 / 230 / 240 V
Voltage range
110 ÷ 276 V (2)
Rated frequency
50 / 60 Hz
Frequency range
±10%
Total harmonic distortion (THDi)
<5%
Power factor
≥0.99
OUTPUT
Power factor
0.9
Voltage
208 / 220 / 230 / 240 V
Static accuracy
±1%
Power (VA/W)
20.000 / 18000
Total harmonic distortion (THDv) Linerar load
≤1%
Total harmonic distortion (THDv) Non~linear load
≤4%
Synchronised frequency
±4 Hz
Frequency
50 / 60 Hz
Frequency accuracy (battery mode)
±0.05 Hz
Total performance in On-line mode
88% ÷ 90%
Admissible overloads
Up to 110% for 10 min; 130% for 1 min
Crest factor
3 a 1
Parallel
Yes, up to 3 units(3)
MANUAL BYPASS
Type
No breaks
STATIC BYPASS
Type and activation criteria
Hybrid
Transfer time
Nil
BATTERY
Protection
Against power surges, undervoltages and alternating current components
Battery type
Not included, Pb-Ca sealed, AGM, maintenance-free
Charge type
I/U (constant current/constant voltage)
Recharge time
9 hours to 90%
CHARGER
Temperature voltage compensation
Yes
COMMUNICATION
Ports
USB, RS-232 and relay
Intelligent slot
Yes, ready for SNMP / AS400 / RS485-Modbus
Monitoring software
Downloadable for Windows, Unix, Linux and Mac
OTHER FUNCTIONS
Cold start (start-up from batteries)
Yes
OPERATING MODES
Eco-mode
Yes
Frequency converter (CVCF)
Yes(5)
GENERAL
Operating temperature
0º C ÷ 40º C
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
2,400 masl (power degradation up to 5,000 m)
Acoustic noise at 1 metre
< 60 dB
STANDARDS
Safety
EN-IEC 62040-1
Electromagnetic compatibility (EMC)
EN 62040-2 (C3)
Operation
VFI-SS-11 (EN-62040-3)
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
815
Width (mm)
250
Height (mm)
826
WEIGHT
Weight (kg)
38